Which two statements are correct regarding the power an…

Which two statements are correct regarding the power and cooling requirements of a SPARC M5-32 server?

Which two statements are correct regarding the power and cooling requirements of a SPARC M5-32 server?

A.
The airflow is from the front to the back of the server. The approximate server airflow is: Maximum; 4200 CFM Typical: 2500 CFM

B.
Only a raised floor with perforated tiles in front of the server is supported.

C.
Cooling from ceiling vents is not supported.

D.
If using a raised floor, you need to arrange seven perforated tiles in front of the server so thatcold air from the tiles can flow into the server. Each perforated tile
should support an airflow of approximately 600 CFM.

Explanation:
https://docs.oracle.com/cd/E24355_01/html/E41214/z400000f1402692.html



Leave a Reply 0

Your email address will not be published. Required fields are marked *